JHL 3, combination of alkali phosphates and a non-volatile oxygen binding agent (reductonate), which hardly affects the salt content.
Suitable for food processing industry.
Field of application: Boiler plants above 100 °C.
Effect: Alkalization (increase of pH-value), oxygen binding and residual hardness precipitation in boiler feed water.
Dosage: Approx. 100 – 150 ml/m³ make-up water.
Proof: Approx. 5 – 10 mg/l phosphate (PO₄³-), observe boiler guidelines, oxygen-free (sample water cooler required).
Available in the container sizes 25 and 60 litres.
For aluminium/silicon components, the pH value must not exceed 8.5!
Order number |
Model |
---|---|
8838154 | JHL 3, 25 litre container |
8838155 | JHL 3, 60 litre container |
JUDO Oxygen measuring set
Titration kit for determining the residual oxygen content in boiler water or condensate. Concentration range 0 – 10 mg O₂. Sample water cooler required!
Order number 8742172
JUDO Phosphate measuring set
Colour comparison set for the concentration range 0 – 10 P₂O₅/l.
Order number 8742136